High Output UV Lamp / Bulb
The high output germicidal UV lamp / bulb is similar
in design to a normal fluorescent lamp / bulb. It is a 4-pin ceramic base lamp /
bulb with Teflon wiring. The UV lamps are constructed of type “L”, hard glass
quartz which eliminates ozone production. Heat output is low, allowing the UV
lamp to be installed safely in several different locations within the HVAC
system. UV Lamp / bulb life is one year. To maintain top performance, all
UV lamps / bulbs should be replaced yearly.
UV Lamp / Bulb Specifications |
UV Lamp Length |
14.5” |
22” |
UV Lamp base |
4-pin
blue ceramic |
Lamp end cap |
Ceramic |
Lamp
etch |
www.americanairandwater.com |
Lamp Teflon wires |
White 26 awg Teflon |
Etch
Location |
50mm |
50mm |
Lamp Diameter |
15mm |
15mm |
Base Diameter |
18.5mm |
18.5mm |
Operating Current |
800mA |
800mA |
Operating Voltage |
54VAC @ 60Hz |
83.4VAC @ 60Hz |
Starting Voltage |
120VAC @ 60Hz |
120VAC @ 60Hz |
Lamp Wattage |
36W |
54.4W |
Lamp UV Output -
/253.7nm@100hrs/ |
12W |
18.13W |
UV intensity @ 1 m |
106µW/cm² |
173.83µW/cm² |
UV
Intensity @ 1' |
800µW/cm²/sec |
1,100µW/cm² |
UV
lamps effective life |
1
year |
1
year |
|
UV Lamp / Bulb With Retaining Ring
Replacement Ultraviolet Lamp / Bulb
Made in the U.S.A.
WARNING |
UV Lamps should be mounted a
minimum of 30” from heat source if on supply side. Prolonged exposure to UV light
will irritate the eyes and possibly burn the skin. Use protection while the UV
lamps are in operation!
|
|